COMMSTAT 4™ HVAC CONTROLLER
Our most comprehensive HVAC controller for air conditioners or heat pumps in a telecom shelter or enclosure.
A single CommStat 4 will control two redundant air conditioners or heat pumps, but has the capability to be daisy chained with a second CommStat 4 unit for controlling up to four air conditioners or heat pumps in a shelter. The CommStat 4 has seven outputs for remote alarms or notification.
A unique Marvair feature, the Comfort button, allows a service tech to easily change the temperature to provide a comfortable working environment. After 90 minutes, the temperature set points automatically revert back to the programmed temperature set points. The CommStat 4 also stores the last 10 ten faults that were registered.
LEAD/LAG OPERATION
User selectable changeover from 1/2 to 7 days in 1/2 increments. If the lead unit loses power, the lag unit automatically becomes the lead unit with all the set points of the lead unit. A lead swap button alternates the lead and lag unit, allowing service techs to easily check the operation of each unit.
ALARMS
Dry contacts can be used for remote alarm or notification. Relays can be wired Normally Open (NO) or Normally Closed (NC).
High (Line) Voltage
Low (Control) Voltage
Lockout
Low Building Temperature
Smoke alarm
First Stage High Building Temperature
Second Stage High Building Temperature
Aux 1 & Aux 2
FEATURES
-
THERMOSTAT RANGE
Cooling: 65° - 95°F (18° - 35°C) in 1° increments.
Heating: 50° - 80°F (10° - 27°C) in 1° increments.
-
DIFFERENTIAL
Adjustable ON-OFF differential for both Stage 1 and Stage 2
Adjustable changeover differential between heating and cooling.
-
MAXIMUM VOLTAGE
24 VAC
-
INPUTS
Input power
Modem Connection
Control voltage
Line Voltage
Temperature Sensors
Smoke Detector
Hydrogen Detector
Generator Relay
Economizer Mode Status Monitoring
Lockout Relay
Aux 1/ Aux 2
-
EASE OF INSTALLATION
Wiring connection insensitive to phasing of the HVAC units.
Easy terminal connections for thermostat wire.
Remote temperature sensors insure accurate temperature readings.
-
OPERATING RANGE
-40°F through 150°F
(-40°C through 66°C)
-
MINIMUM VOLTAGE
18 VAC
-
MAXIMUM VOLTAGE
30 VAC
-
EASE OF INSTALLATION
Wiring connection insensitive to phasing of the HVAC units.
Easy terminal connections for thermostat wire.
Remote temperature sensors insure accurate temperature readings.